The test at a glance
A model of power through low-voltage feeders that first learned from Living Worlds' simulation, and then from a handful of real measurements, predicted 30 feeders that no model had measured, over a year it had not seen, better than the same model trained on real measurements alone. With 5 measured feeders it made 0.712 normalised error against 0.880; with 10, 0.605 against 0.695; with 80 the two were level. The same model taught by a deliberately wrong simulation did worse than either. One region and operator (Baden-Wuerttemberg), 30 feeders, scored on hourly means. Registered before the test year was read; scored once. Data: FeederBW v1.1, Netze BW and KIT (Treutlein et al., Scientific Data 13, 1283, 2026), CC BY 4.0.
Protocol, result and scorer
Next
The same test on feeders from another operator.